Unstable pressure transmitter output?
2020-02-05
Unstable pressure source: Check whether the pressure of the pressurization system is unstable
No ground wire: Ground wire for pressure transmitter and equipment
The installation position of the transmitter has a large magnetic field: Install shielding cover or replace installation position
The cable is too long and passes through the magnetic field:Replace cable routing position
Transmitter water or steam: Put the transmitter into the temperature box when the transmitter is notpowered on, and heat it to 65 ℃ for drying
There are stone sand or sundries in the pressurized pipeline: Clear
Pressure medium temperature is too high: Check whether the medium temperature is within the allowable range of the transmitter
Foshan puliang Electronic Co., Ltd

Tel:0757-26619568 Fax: 0757-26619508

24-hour online technical support:13790092618

Cloud platform:www.puliangiot.com

Address:501, block 8, phase 5, Rongli tianfulai industrial city, Ronggui town, Shunde District, Foshan City

Copyright©Foshan puliang Electronic Co., Ltd